|
Permit needed for:
- Bath exhaust fans
- New Supply outlets
- Duct
- Clothes dryer exhaust
- Changing of furnace flue vent
BATH EXHAUST
Bath exhaust fans are required in all restrooms. Duct must be increased
to 4” diameter instead of 3” diameter, if there is an elbow
and the duct is more than 3’ long. The exhaust duct must terminate
outside of the house.
COMBUSTION AIR
The mechanical code most frequently ignored during remodeling is the
combustion air requirements to the furnace room. As walls are built
and finished, the combustion air supplied to the furnace and water heater
is decreased. When this happens, some provision must be made to replenish
this lost volume of air. This may be accomplished by either one of two
methods: high/low grills or outside air.
High/Low Grills:
By adding the total input BTUs of the furnace and water heater (marked
on nameplate), you can calculate the size of combustion air grills
to be installed (within 12” of ceiling and floor). These grills
are installed through the walls to replenish the combustion air volume
to the furnace room.
Outside air:
An alternative method is to provide an opening into the furnace room
from the outside of the house to replenish the combustion air. The
total input BTUs will determine the size of opening from the outside.
Consult with a registered Heating Contractor or an Inspector with
the Department of Building & Safety for assistance in these calculations.
DRYER EXHAUST DUCTS:
Dryer exhaust duct must be metal and have a smooth interior surface
wherever it is concealed. You may use 6’ of flexible duct connected
to your dryer if it is not concealed in the wall or ceiling. Dryer exhaust
ducts may be 25’ long using two 90 degree elbows. Each additional
90 degree elbows will decrease the length of the duct allowed by 8’.
Do not use screw to fasten dryer duct. You may use short pop rivets
or a strong “furnace” or “foil” tape.
FURNACE:
If you are building walls or doors close to your furnace, you must maintain
proper clearances. Thirty inches is required in from of the furnace
for access to repair. The sides and back of the furnace will have clearance
ratings marked on the name plate. These are usually 1". A door
may be built no closer than 6" in front of a furnace (provided
the door opens to provide 30" clearance". The supply duct
extending horizontally away from your furnace must be 1" away from
combustibles for the first 3'. The furnace flue pipe requires 6"
clearance to combustible if it is single wall pipe. One inch clearance
is required for type "B" double wall flue pipe.
FURNACE ACCESS:
You may not have a furnace in a bedroom or a bathroom (shower or tub
room). You may not pass through a bedroom or a bathroom to access the
furnace room.
|